🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

110 Amp Wire Size at 125 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 110 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)2 AWG33.62 mm² · Drop: 2.22%
Aluminum Wire (≤3% Drop)1/0 AWGDrop: 5.53V (2.3%)
Voltage at Load End234.7 VLoss: 5.34 V (586.9 W)
Power & Breaker (125%)26.4 kW150A Breaker Recommended

All AWG & kcmil Wire Gauges for 110 Amps at 125 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A86.24 V (35.93%)153.8 V142.25 V (59.27%)9486.2 WDrop/Amp High
12 AWG3.31 mm²20 A54.19 V (22.58%)185.8 V89.39 V (37.25%)5961.1 WDrop/Amp High
10 AWG5.26 mm²30 A34.1 V (14.21%)205.9 V56.25 V (23.44%)3751.2 WDrop/Amp High
8 AWG8.37 mm²50 A21.43 V (8.93%)218.6 V35.35 V (14.73%)2357.4 WDrop/Amp High
6 AWG13.3 mm²65 A13.49 V (5.62%)226.5 V22.25 V (9.27%)1483.6 WDrop/Amp High
4 AWG21.15 mm²85 A8.48 V (3.53%)231.5 V13.99 V (5.83%)932.9 WDrop/Amp High
3 AWG26.67 mm²100 A6.73 V (2.8%)233.3 V11.09 V (4.62%)739.8 WDrop/Amp High
2 AWG33.62 mm²115 A5.34 V (2.22%)234.7 V8.8 V (3.67%)586.9 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A4.23 V (1.76%)235.8 V6.98 V (2.91%)465.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A3.35 V (1.4%)236.6 V5.53 V (2.3%)368.9 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.66 V (1.11%)237.3 V4.39 V (1.83%)292.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A2.11 V (0.88%)237.9 V3.48 V (1.45%)232.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.67 V (0.7%)238.3 V2.76 V (1.15%)184.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.42 V (0.59%)238.6 V2.34 V (0.97%)155.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.18 V (0.49%)238.8 V1.95 V (0.81%)129.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.01 V (0.42%)239.0 V1.67 V (0.7%)111.3 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.88 V (0.37%)239.1 V1.46 V (0.61%)97.3 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.71 V (0.29%)239.3 V1.17 V (0.49%)77.9 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.59 V (0.25%)239.4 V0.97 V (0.41%)64.9 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.47 V (0.2%)239.5 V0.78 V (0.32%)51.9 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.35 V (0.15%)239.6 V0.58 V (0.24%)38.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 110 amps at 125 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 110A load over 125 feet one-way at 240V (1-Phase), you need 2 AWG copper wire. This produces a voltage drop of 5.34V (2.22%) and delivers 234.7V at the load.

What size aluminum wire is required for 110 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1/0 AWG to maintain voltage drop at 5.53V (2.3%).

What breaker size is needed for a 110A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (110A × 1.25 = 137.5A), which corresponds to a standard 150A circuit breaker.